300/500V SR Insulated, LSZH Sheathed, Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore)
FFX200 05SOZ1-U/R PH30/PH60 (CU/SR/OSCR/LSZH 300/500V Class 1/2)
APPLICATION
300/500V SR Insulated, LSZH Sheathed, Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore) are
primarily intended for use in the following applications:
BS 5266-1 for emergency lighting of premises.
BS 5839-1 for fire detection and fire alarm systems in and around building.
BS 5839-8 for voice alarm systems.
BS 5839-9 for emergency voice communication systems.
STANDARDS
Basic design to BS 7629-1:2015

FIRE PERFORMANCE
| Circuit Integrity | BS 6387; BS EN50200 |
|---|---|
Flame Retardance (single vertical wire or cable test) |
IEC 60332-1-2; EN 60332-1-2 |
Reduced fire Propagation (Vertically-mounted bundled wires & cables test) |
IEC 60332-3-24; EN 60332-3-24 |
Halogen free |
IEC 60754-1; EN 50267-2-1 |
No corrosive Gas emission |
IEC 60754-2; EN 50267-2-2 |
Minimum smoke emission |
IEC 61034-2; EN 61034-2 |
VOLTAGE RATING
300/500V
CABLE CONSTRUCTION
Conductor : Copper conductor according to BS EN 60228 class 1/2.
Insulation : Fire resistant special ceramized silicone rubber compound type EI 2 as per BS EN 50363-1.
Screened : One or more metallic or laminated metallic tape(s) shall be applied, either longitudinally or helically or
a combination of both, with the metallic element in contact with the uninsulated circuit protective conductor or
drain wire.
Circuit Protective Conductor : Uninsulated tinned copper conductor of the same section and class as the
insulated conductors in the two,three and four cores cables.
Sheath : Extruded LSZH type LTS 3 according to BS 7655-6.1.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite
properties can be offered as option.
COLOUR CODE
Insulation Colour :
| Number of cores | Core colours or numbering |
|---|---|
2 cores+uninsulated circuit protective conductor |
Brown, Blue or Brown, Brown |
3 cores+uninsulated circuit protective conductor |
Brown, Black, Grey |
4 cores+uninsulated circuit protective conductor |
Brown, Blue, Black, Grey |
7, 12 and19 cores+uninsulated drain wire |
Numbers 1, 2, 3, 4, 5, 6, 7 and upwards or, for identification by colour, an identical colour(excluding brown and black),except for two adjacent cores in each layer distinctively coloured brown and black. |
Sheath Colour : Colours upon request.
PHYSICAL AND THERMAL PROPERTIES
Maximum temperature range during operation : 60°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 6 x Overall Diameter
CONSTRUCTION PARAMETERS
Conductor |
FFX200 05SOZ1-U/R PH30/PH60 |
|||||
|---|---|---|---|---|---|---|
No. of Cores × Cross-sectional Area |
Conductor Class |
Nominal Insulation Thickness |
CPC Nominal Cross-sectional Area |
Nominal Sheath Thickness |
Approx. Overall Diameter |
Approx. Weight |
no.×mm² |
|
mm |
mm² |
mm |
mm |
kg/km |
2 cores |
||||||
2x1.0 |
1/2 |
0.6 |
1.0 |
0.9 |
8.0 |
78 |
2x1.5 |
1/2 |
0.7 |
1.5 |
0.9 |
8.5 |
103 |
2x2.5 |
1/2 |
0.8 |
2.5 |
1.0 |
10.5 |
150 |
2x4.0 |
1/2 |
0.8 |
4.0 |
1.1 |
12.5 |
212 |
3 cores |
||||||
3x1.5 |
1/2 |
0.7 |
1.5 |
0.9 |
9.5 |
130 |
3x2.5 |
1/2 |
0.8 |
2.5 |
1.0 |
11.5 |
191 |
3x4.0 |
1/2 |
0.8 |
4.0 |
1.1 |
13.5 |
273 |
4 cores |
||||||
4x1.5 |
1/2 |
0.7 |
1.5 |
1.0 |
10.5 |
165 |
4x2.5 |
1/2 |
0.8 |
2.5 |
1.1 |
12.0 |
242 |
4x4.0 |
1/2 |
0.8 |
4.0 |
1.2 |
15.0 |
344 |
7 cores |
||||||
7x1.5 |
1/2 |
0.7 |
0.5 |
1.1 |
12.5 |
257 |
7x2.5 |
1/2 |
0.8 |
0.5 |
1.2 |
15.0 |
568 |
12 cores |
||||||
12x1.5 |
1/2 |
0.7 |
0.5 |
1.2 |
16.0 |
414 |
12x2.5 |
1/2 |
0.8 |
0.5 |
1.4 |
20.0 |
886 |
19 cores |
||||||
19x1.5 |
1/2 |
0.7 |
0.5 |
1.3 |
19.0 |
617 |
Note: The parameters listed above are nominal values as per cable standards. Actual values may vary due to material and manufacturing process variations. For precise specifications or customized requirements, please contact us for further information
ELECTRICAL PROPERTIES
Conductor operating temperature : 70°C
Ambient temperature : 30°C
Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D2A
Conductor cross-sectional area |
Ref. Method A (enclosed in conduit in thermally insulating wall etc) |
Ref. Method B (enclosed in conduit on a wall or in trunking etc) |
Ref. Method C (clipped direct) |
Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical) |
||||
|---|---|---|---|---|---|---|---|---|
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, singlephase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
1 two-core cable*, single-phase a.c. or d.c. |
1 three-core or 1 four-core cable*, three-phase a.c. |
|
1 |
2 |
3 |
4 |
5 |
6 |
7 |
8 |
9 |
mm² |
A |
A |
A |
A |
A |
A |
A |
A |
1.0 |
11 |
10 |
13 |
11.5 |
15 |
13.5 |
17 |
14.5 |
1.5 |
14 |
13 |
16.5 |
15 |
19.5 |
17.5 |
22 |
18.5 |
2.5 |
18.5 |
17.5 |
23 |
20 |
27 |
24 |
30 |
25 |
4 |
25 |
23 |
30 |
27 |
36 |
32 |
40 |
34 |
Note: *With or without a protective conductor.
Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D2B
Conductor cross-sectional area |
Two-core cable d.c. |
Two-core cable single-phase a.c. |
Three- or four-core cable, three-phase a.c. |
|---|---|---|---|
1 |
2 |
3 |
4 |
mm² |
mV/A/m |
mV/A/m |
mV/A/m |
1.0 |
44 |
44 |
38 |
1.5 |
29 |
29 |
25 |
2.5 |
18 |
18 |
15 |
4 |
11 |
11 |
9.5 |